As stated above, they have their own unique address that is assigned when the system is programmed. This address is assigned to the transponder at installation via a DIP or rotary switch.
Again, the variety of modules, sensors and data gathering panels is limited only by the manufacturer’s imagination and technical expertise. Addressable smoke or heat detectors are usually referred to as “sensors” to distinguish them from conventional detectors. These sensors may either contain an integral address switch, or in older or economical systems, they may simply be conventional detectors installed in an addressable base. Conventional detectors installed in an addressable base would constitute an “Addressable System”. Smoke sensors containing microprocessors now report their status to the CPU. While a conventional
detector has only two conditions: Alarm or Normal, the newest sensors can notify the CPU that they “smell smoke”, or are approaching an alarm condition, or signal that they are dirty and require cleaning, etc. Their sensitivity can be varied by the control panel and new features are being announced continually.
Systems employing these sensors are known as “Analog Addressable” since their condition is displayed in an analog fashion rather than a digital “normal” or “alarm” condition.
Many people erroneously use the term “Analog Addressable” to describe all devices connected to an SLC, but technically this term does not apply to devices such as manual pull stations or electronic addressable heat detec- tors that have been employed in these systems until now. Even though heat sensors may be addressable and signal an alarm via the SLC, they can only report the two states, alarm or normal. Now appearing on the horizon are heat sensors that can indicate their changing condition in the same manner as a smoke sensor, such as reporting an increase in ambient heat, so nothing is etched in concrete regarding the ability and features of these sensors.
Monitor modules have their own as- signed addresses and commonly feature a conventional initiating circuit complete with an end of line resistor. Conventional dry contact initiating devices are connected to this circuit. These may be electromechanical heat detectors, manual pull stations, water- flow switches, etc. When any of these devices go into alarm, the monitor mod- ule provides a collective address for the devices on its circuit. Newer modules are now available featuring multiple initiating circuits and provide different addresses for each of these circuits.
Some modules are small enough to fit inside a device housing or backbox. These modules are usually intended for connection to a single initiating device. An example of this would be a module installed inside a pull station, providing an address for the station. Some manufacturers preassemble the monitor modules into pull stations, etc. while others prefer to sell the module only, and allow the installer to connect the modules in the field.
Other monitor modules have an initiating 2-wire circuit that may be extended considerably, and can accommodate a specified number of conventional 2- wire compatible conventional smoke detectors in addition to a number of dry contact initiating devices. This module provides one address for each circuit, and is useful in large areas, such as auditoriums, atriums or gymnasiums where only a collective address is needed to guide fire-fighting forces to the source of the fire.
Data gathering panels have been used since the earliest days of addressable systems. These panels resemble a small conventional fire alarm control panel and contain a number of conventional initiating circuits, battery standby, etc. These panels in effect provide a subsystem with its own address, but I wouldn’t be surprised if some of the latest ones provide multiple addresses, one for each initiating circuit.
Output or control modules may also be installed anywhere on the SLC. These modules likewise have their own unique address and may be programmed to perform a function in the event of an alarm or trouble on any individual or combination of monitor modules or sensors. These control modules may contain dry contacts that transfer on command, but again, new configurations are arriving on the mar- ket on a daily basis. Some will accept an audio input and provide supervised loudspeaker appliance circuits, while others will supervise and operate notification appliance circuits. Still others can be used to energize releasing solenoids or provide smoke damper operation in smoke control systems.
System programming also varies with the manufacturer. In the earlier days some small system manufacturers used burn-in chips, or PROMS for the programming. Larger systems are programmed via software. In these sys- tems, the programming is often done in the office on a computer and then down- loaded to the control panel in the field via lap-top computer. Some software programs are user friendly while others are not, and usually require specialized training. The easiest ones to use contain drop-down menus and the programmer need only to literally “fill in the blanks” in order to complete the program.
When the system is programmed, a description of the device can also be included (in systems with alpha-numeric display) such as “ionization sensor, main lobby, right wing”. Thus, when the device goes into alarm, this message will display on the readout, giving firefighters explicit information as to the location of the fire.
OPERATION SUMMARY
The microprocessor in the main control interrogates or polls the transponders in sequence, with only nanoseconds being required for each device or cluster of sensors. When a transponder is polled, it responds that it is either in a normal state or in alarm. In Analog Address- able Systems, a transponder installed in a smoke sensor will also indicate the condition of the sensor, such as “dirty”, approaching alarm condition, etc. If the transponder is disconnected for any reason (malfunction or break in the wir- ing) the panel will show a system trouble and show a “device missing” message (or code) on the display, which will give a specific location of the device. Other fault messages can be for an SLC break, circuit shorted, etc. Some systems may indicate a circuit break by displaying a list of missing addresses located beyond the break or short.
One disadvantage of the addressable system is that polling or interrogation consumes a fraction of a second per device polled. If a substantial number of devices are installed in an individual signaling line circuit, a considerable amount of time could elapse until an alarm is processed. Present control panel standards require a maximum of 5 seconds for a panel to process an alarm after it is received from an initiating device. The development of sensors that will operate in a cluster mode has made this an easier matter. However, it is common to use a larger number of SLCs with fewer devices installed on them rather than have one huge SLC with numerous devices.
The addressable system is also programmed to make specific responses depending on the device activated. Thus the system can process an alarm from a sensor with complete alarm response including notification of the fire department and operation of elevator capture devices, operation of smoke dampers, etc. It may also process a supervisory signal from a tamper switch with sounding of dedicated appliances only, or indicate that a control module has been activated and has performed its required function.